(1) the capacitor Banks should adopt appropriate protective measures, such as the balancing differential relay protection or using instantaneous over-current relay protection, for more than 3.15 kV capacitor, a separate device must be on each capacitor fuse, fuse rated current should be according to the characteristics of fuse and plug flow to selected, when the general is 1.5 times the rated current of the capacitor is appropriate, in order to prevent the capacitor tank explosion.
(2) in addition to the above points out that the protection of the form, if necessary, you can also make the following several kinds of protection:4) in the high voltage network, more than 20, when a short circuit current and short circuit current protection device or fuse cannot reliably protect of short circuit, the single phase short circuit protection should be adopted.
(4) the capacitor is not allowed to furnish automatic reclosing device, instead should be installed without pressure release automatic tripping device.Is mainly due to the need of capacitor discharge time, when the switch of capacitor group trip, if reclosing immediately, is too late to discharge the capacitor, the capacitor may in some feelings and reclosing voltage polarity opposite electric charge, it will make the closing moment produces huge impact current, resulting in capacitor shell expansion, fuel injection, and even explode.